Application |
Compressors with individually led out PTC sensors |
Functions |
Motor temperature static |
Supply voltage |
AC 120/240V |
Undervoltage limits |
85V (120V mains) / 170V (240V mains) |
Permitted ambient temperature |
-40…+70°C |
Temperature measuring circuits: Type |
3 separate inputs for PTC sensors acc. to DIN 44081, DIN 44082 |
Temperature measuring circuits: R_trip, static |
13kΩ ±3kΩ |
Temperature measuring circuits: R_reset |
3.25kΩ ±0.5kΩ |
Temperature measuring circuits: Max. length connection line |
30m |
Relay: Connection |
Refer to wiring diagram Max. 2,5A C300 |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Interface |
Diagnose port (DP) |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
6.3mm flat plugs |
Housing material |
PA glass-fibre-reinforced |
Mounting |
Screw mounted |
Dimensions |
Refer to dimensions in mm |
Weight |
Approx. 200g |
Check base |
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval |
UL File No. E75899 cURus |