Application
|
Extended service life of system due to temperature and current monitoring
|
Supply voltage
|
AC 115-240V
|
Permitted ambient temperature
|
-30...+70°C
|
Reset delay: Overvoltage
|
1min ±6s
|
Reset of reset delay
|
Main reset >5s only possible if there is no error current
|
Relay: Connection
|
240V ~ 2.5A C300Min. 24V ~ / 20mA
|
Relay: Mechanical service life
|
Approx. 1 million switching cycles
|
Interface
|
Diagnose port (DP)
|
Protection class acc. To EN 60529
|
IP00
|
Connection type
|
6.3mm flat plugs
|
Housing material
|
PA glass-fibre-reinforced
|
Mounting
|
Screw mounted
|
Dimensions
|
See dimensions in mm
|
Weight
|
Approx. 200g
|
Check base
|
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2
|
Mains voltage monitoring: Monitoring range 1
|
AC 110-120V
|
Mains voltage monitoring: Monitoring range 1, Mains voltage recognition
|
≤150V
|
Mains voltage monitoring: Monitoring range 1, Accuracy
|
±5% of the measuring range
|
Mains voltage monitoring: Monitoring range 1, Undervoltage preliminary warning
|
<103V
|
Mains voltage monitoring: Monitoring range 1, Undervoltage shutdown
|
<98V
|
Mains voltage monitoring: Monitoring range 1, Overvoltage preliminary warning
|
>127V
|
Mains voltage monitoring: Monitoring range 1, Overvoltage shutdown
|
>132V
|
Mains voltage monitoring: Monitoring range 2
|
AC 220-240V
|
Mains voltage monitoring: Monitoring range 2, Mains voltage recognition
|
>150V
|
Mains voltage monitoring: Monitoring range 2, Accuracy
|
±5% of the measuring range
|
Mains voltage monitoring: Monitoring range 2, Undervoltage preliminary warning
|
<187V
|
Mains voltage monitoring: Monitoring range 2, Undervoltage shutdown
|
<177V
|
Mains voltage monitoring: Monitoring range 2, Overvoltage preliminary warning
|
>244V
|
Mains voltage monitoring: Monitoring range 2, Overvoltage shutdown
|
>265V
|
Reset delay: Undervoltage
|
1min ±6s
|