Application |
Compressors with direction of rotation essential for function and oil management |
Functions |
Motor temperature static, Oil temperature, Short circuit, Phase monitoring, phase sequence, phase asymmetry, Lock-out, operating recognition |
Supply voltage |
AC/DC 24-240V |
Permitted ambient temperature |
-30...+70°C |
Temperature measuring circuits: Type |
NTC Sensor, R25 = 5kΩ, B25/85 = 3992K |
Temperature measuring circuits: Max. length connection line |
10m |
Temperature measuring circuits: Measuring range |
0-135°C |
Temperature measuring circuits: Accuracy |
±3% of the measuring range |
Temperature measuring circuits: Motor temperature, activate |
121°C |
Temperature measuring circuits: Motor temperature, reset |
109°C |
Temperature measuring circuits: Oil temperature, activate |
96°C |
Temperature measuring circuits: Oiltemperature, reset |
85°C |
Short circuit monitoring system PTC |
Typically <55? |
Short circuit monitoring system NTC |
Typically <55Ω |
Input oil flow oil level and oil filter soiling: Designed for |
Potential-free normally open contact (typ. 3.3V, 1mA) |
Input oil flow oil level and oil filter soiling: Max. length connection line |
10m |
Motor voltage |
3 AC 20-100Hz 80-690V ±10% |
Phase monitoring: Phase sequence |
Active about 1s after motor start for about 5s |
Phase monitoring: Inactive |
After motor stop for approx. 10s |
Phase monitoring: Phase asymmetry |
Active about 1s after the motor start until the motor stop |
Operating with frequency converters |
Suitable |
Reset delay: Motor temperature static |
10min ±2min, 60min ±12min, Verriegelt |
Reset delay: Incorrect phase sequence |
Locked |
Reset delay: Oil temperature |
Undelayed |
Reset delay: Phase asymmetry |
5min ±1min, Verriegelt |
Reset delay: Oil flow |
5min ±1min, Verriegelt |
Reset delay: Oil filter |
Locked |
Reset delay: Oil level |
Locked |
Resetting the lock or the reset delay |
Main reset >5s or reset by keyboard only possible if there is no error current |
External button: Designed for |
Potential-free normally open contact (typ. 3.3V, 1mA) |
External button: Max. length connection line |
1m |
Relay: Connection |
AC 240V 2.5A C300 at least AC/DC 24V 20mA |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Interface |
Diagnose port (DP) |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
6.3mm flat plugs (L1-L3, L and N), push-in spring terminals, 0.25-0.75mm2 |
Housing material |
PA glass-fibre-reinforced |
Mounting |
Screw mounted |
Dimensions |
Refer to dimensions in mm |
Weight |
Approx. 150g |
Check base |
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval |