Application |
Electrical mashines |
Supply voltage |
AC 24-240V |
Permitted ambient temperature |
-30...+70°C |
Temperature measuring circuits: Type |
1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series |
Temperature measuring circuits: R_25, total |
<1.8kΩ |
Temperature measuring circuits: R_trip, static |
4.5kΩ ±20% |
Temperature measuring circuits: R_reset |
2.75kΩ ±20% |
Temperature measuring circuits: Max. length connection line |
10m |
Phase monitoring: Phase sequence |
Active for 5s. approx. 1s after connection of the network |
Phase monitoring: Phase asymmetry |
Active in approx. 1s after connection of the network |
Phase monitoring: Limit value switch-off asymmetry |
25% ±3% |
Phase monitoring: Triggering delay time |
Approx. 15s |
Phase monitoring: Limit value switch-off failure |
50% ±3% |
Reset delay: Undervoltage |
5min ±1min |
Reset delay: Overvoltage |
5min ±1min |
Reset delay: Temperature measure circuits |
Undelayed |
Reset delay: Incorrect phase sequence |
Locked |
Reset delay: Phase failure |
5min ±1min |
Reset delay: Phase asymmetry |
5min ±1min |
Resetting the lock or the reset delay |
Main reset >5s or reset by keyboard only possible if there is no error current |
Relay: Connection |
AC 240V 2.5A C300 at least AC/DC 24V 20mA, AC 240V 2.5A C300 at least AC/DC 100mV 0.5mA |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Interface |
Diagnose port (DP) |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
6.3mm flat plugs |
Housing material |
PA glass-fibre-reinforced |
Mounting |
Screw mounted |
Dimensions |
Refer to dimensions in mm |
Weight |
Approx. 200g |
Check base |
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval |
UL File No. E75899 cURus |
Mains voltage monitoring: Monitoring range |
AC 50/60Hz, 380-400V |
Mains voltage monitoring: Accuracy |
±15% of the measuring range |
Mains voltage monitoring: Undervoltage limit 1 |
285V |
Mains voltage monitoring: Undervoltage limit 2 |
266V |
Mains voltage monitoring: Overvoltage limit 1 |
460V |
Mains voltage monitoring: Overvoltage limit 2 |
480V |
Mains voltage monitoring: Triggering delay time 1 |
Approx. 120s |
Mains voltage monitoring: Triggering delay time 2 |
Approx. 15s |