Application |
Extended service life of system due to temperature and current monitoring |
Supply voltage |
AC 115-240V |
Permitted ambient temperature |
-30...+70°C |
Temperature measuring circuits: Type |
1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series |
Temperature measuring circuits: R_25, total |
<1.8kΩ |
Temperature measuring circuits: R_trip, static |
4.5kΩ ±20% |
Temperature measuring circuits: R_reset |
2.75kΩ ±20% |
Temperature measuring circuits: Max. length connection line |
10m |
Short circuit monitoring system PTC |
Typically <30Ω |
Reset delay: Motor temperature static |
30min ±5min |
Reset delay: Overvoltage |
1min ±6s |
Reset of reset delay |
Main reset >5s only possible if there is no error current |
Relay: Connection |
240V ~ 2.5A C300Min. 24V ~ / 20mA |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Interface |
Diagnose port (DP) |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
6.3mm flat plugs |
Housing material |
PA glass-fibre-reinforced |
Mounting |
Screw mounted |
Dimensions |
See dimensions in mm |
Weight |
Approx. 200g |
Check base |
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Mains voltage monitoring: Monitoring range 1 |
AC 110-120V |
Mains voltage monitoring: Monitoring range 1, Mains voltage recognition |
≤150V |
Mains voltage monitoring: Monitoring range 1, Accuracy |
±5% of the measuring range |
Mains voltage monitoring: Monitoring range 1, Undervoltage preliminary warning |
<103V |
Mains voltage monitoring: Monitoring range 1, Undervoltage shutdown |
<98V |
Mains voltage monitoring: Monitoring range 1, Overvoltage preliminary warning |
>127V |
Mains voltage monitoring: Monitoring range 1, Overvoltage shutdown |
>132V |
Mains voltage monitoring: Monitoring range 2 |
AC 220-240V |
Mains voltage monitoring: Monitoring range 2, Mains voltage recognition |
>150V |
Mains voltage monitoring: Monitoring range 2, Accuracy |
±5% of the measuring range |
Mains voltage monitoring: Monitoring range 2, Undervoltage preliminary warning |
<187V |
Mains voltage monitoring: Monitoring range 2, Undervoltage shutdown |
<177V |
Mains voltage monitoring: Monitoring range 2, Overvoltage preliminary warning |
>244V |
Mains voltage monitoring: Monitoring range 2, Overvoltage shutdown |
>265V |
Reset delay: Undervoltage |
1min ±6s |