Application |
Compressors with direction of rotation essential for function |
Functions |
Motor temperature static, Phase sequence, phase failure, Lock-out, phase monitoring |
Supply voltage |
AC 24-240V |
Permitted ambient temperature |
-30...+70°C |
Temperature measuring circuits: Type |
1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series |
Temperature measuring circuits: R_25, total |
<1.8kΩ |
Temperature measuring circuits: R_trip, static |
4.5kΩ ±20% |
Temperature measuring circuits: R_reset |
2.75kΩ ±20% |
Temperature measuring circuits: Max. length connection line |
30m |
Motor voltage |
3 AC 50/60Hz 200-575V ±10% |
Phase monitoring: Phase sequence |
Active about 1s after motor start for about 5s |
Phase monitoring: Phase failure |
Active about 1s after motor start for about 5s |
Phase monitoring: Inactive |
After motor stop for approx. 20s |
Operating with frequency converters |
Not suitable |
Reset delay: Motor temperature static |
5min ±1min |
Reset delay: Incorrect phase sequence |
Locked |
Reset delay: Phase failure |
Locked |
Resetting the lock or the reset delay |
Main reset >5s only possible if there is no error current |
Relay: Connection |
AC 240V 2.5A C300 at least AC/DC 24V 20mA |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Interface |
Diagnose port (DP) |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
6.3mm flat plugs |
Housing material |
PA glass-fibre-reinforced |
Mounting |
Screw mounted |
Dimensions |
Refer to dimensions in mm |
Weight |
Approx. 200g |
Check base |
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval |
UL File No. E75899 cURus |